Riello ups dld 330 manual

2 INTRODUCTION Congratulations on purchasing a UPS Sentinel Pro product and welcome to Riello UPS!To use the support service offered by Riello UPS, visit the site www.riello-ups.com The company is highly specialised in the development and production of uninterruptible power supplies (UPSs). Riello DLD 600 UM6K600735RUB Manuale Utente. Codici prodotto. Scarica Like. Schermo intero Standard. The uPs is designed to support a wide range of applications. Pagina 3 MODELS DLD 330 DLD 400 DLD 500 DLD 600 DLD 800 DLD 1000 POWER 3300VA/2300W 4000VA/2400W 5000VA/3500W 6000VA/4200W 8000VA/6400W.

  • Riello Multi Plus UPS available from EcoPowerSupplies. User manual, cd-rom containing the UPS management software, serial connecting cable, 4 battery fuses (to be inserted in the 'SWBATT' fuse holders), door key. P OSITIONING THE UPS. Riello Multi Plus 30-40kVA Manual.
  • Start Uninterruptible Power Supplies (UPSs) Riello DLD 330 uninterruptible power supply (UPS) More Sharing Services Share This is a demo of a seamless insert of an Icecat LIVE product data-sheet in your website.

Riello Ups Dld 330 User Manual 2016

Local Area Networks (LAN) Servers Data centers Industrial PLCs Electronic Point Of Sale (EPOS) Emergency devices (lights/alarms) Electro-medical devices
DIALOG Dual
NETWORK RANGE
3,3-6KVA single/single-phase
The DIALOG DUAL range is available in 3300-40005000-6000VA models, with on-line double conversion (VFI) technology. The DIALOG DUAL range may be placed directly on the floor or mounted in 19” rackmount cabinets such as the Multi Shelter range. In terms of technology, features (selectable On-line, Economy and Smart Active operating modes), and diagnostics such as the digital display, RS232 and USB interfaces, network adaptor card option and PowerShield2 software included, DIALOG DUAL is easily the best solution for protecting “mission critical” applications requiring the highest levels of reliability. DIALOG DUAL is ideally suited for a whole range of applications from IT to security.
CHARACTERISTICS • the UPS can be installed as a floor standing tower or 19” rack mount UPS. The front panel digital display can be pulled out (using the keys provided) and rotated to suite the installation format • reliable, filtered, stabilised and regulated sinewave output (double conversion technology VFI in conformity with IEC 62040-3 specifications) with filters for atmospheric disturbance suppression • low noise level (20kHZ, above the audible range) • optional bolt-on maintenance bypass (DLD 500/600 models) to allow service without disruption to the loads • user selectable operating modes in addition to true on-line mode: – Economy Mode: selects Line Interactive VI technology to power non-critical loads from mains and archieve up to 98% operating efficiency – Smart Active Mode: the UPS selects automatically whether to operate in On-line VFI or Line Interactive VI mode depending on the stability of the mains supply – Emergency: the UPS can be programmed to work only when the mains fails - suitable for emergency lighting – Frequency conversion 50 or 60Hz • output voltage selection: 220-230-240Vac • auto restart when mains power returns programmed using the front panel or using PowerShield² software
1. 2. 3. 4.
1 2 3 4
7
5
8 6
9 10
STATUS Normal UPS on mains UPS on battery Load on bypass
5. ALARM UPS shutdown (permanent) Standby (flashing) 6. MEASUREMENTS Input voltage and frequency Output voltage and frequency Battery voltage Output current Output load (%) Battery charge (%) Remaining back-up time Internal temperature CONFIGURATIONS 7. Timer set 8. Frequency selected 9. Voltage selected 10. Operating mode selected
• bypass on: when the UPS is switched off, it automatically goes into bypass mode to charge the batteries • automatic power down due to minimum load • end of battery discharge pre-alarm • delayed start up • PowerShare output socket (2x10A IEC) functionality on DLD 500/600 models • guaranteed output quality even with typical distorting IT loads with crest factors of 3:1 • rephasing of load as the UPS has an input power factor close to 1, with a sinusoidal input current
Hot Swap battery
• • • • • • • • •
completely digitally controlled automatic bypass with no break in power supply use of IMS (Insulated Metallic Substrates) modules status, measurements, and alarms available on the standard backlit display UPS can be updated digitally (flash upgradeable) highly reliable battery performance (automatic and manual battery tests) Unique Low Ripple Current Discharge (LRCD) to help prolong battery life hot-swap user replaceable batteries no limit extendable back-up time using modular design Battery Extension Packs
1. USB port 2. Serial port 3. Interface card slot SNMP or additional RS232 ports 4. Input thermal protection re-set 5. Input hardwired gland 6. Output hardwired glands 7. Battery extension pack connector
7
2
1
3
4
DIALOG Dual
5
• increased ride through (without batteries) on mains breaks up to 40ms and for fluctuations ranging from 84 to 276Vac • input protected by resettable thermally activated switch • Back-feed protection: to avoid current being fed back into the mains should a fault occur • increased short circuit current on the bypass • increased overload capacity: 150% on inverter even when mains supply has failed • performance guaranteed in temperatures up to 40°C • manual switch over to bypass • two IEC output plugs with thermal protection (DLD500-600).
6
Rear panel DLD500-600
1
2
3
4
MICROSOFT CERTIFIED PRODUCT 5
6 7
Rear panel DLD330-400
DLD330-400 hot swap batteries
ADVANCED COMMUNICATION • advanced, multi-platform communication for all operating systems and network environments: PowerShield² supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT4.0, 2000, 2003, Me, XP, Mac OSX, 9.X, Linux, Novell operating systems. The UPS is supplied with a communications cable for ’Plug and Play’ PC connection • plug & play feature • USB port • RS232 serial port • slot for one of the following interface cards: - Network adapter (Netman 102) - Multiplexer (Multicom 352) - JBUS/MODBUS interface (Multicom 302) - RS232/USB card (Multicom 362) - RS232/EPO* (Multicom 372) - Dry contacts card/EPO* (Multicom 382) • Microsoft certification. * EPO is standard on DLD500-600 models. 2-YEAR WARRANTY
DLD500-600 hot swap batteries
External bypass option
Standard connection
DIALOG Dual
MODELS
DLD 330
DLD 400
DLD 500
DLD 600
POWER
3300VA/2300W
4000VA/2400W
5000VA/3500W
6000VA/4200W
INPUT Rated voltage
220 - 230 - 240 Vac
Minimum voltage
164 Vac @ load 100%
Rated frequency Power factor Current distortion
84 Vac @ load 50%
50/60 Hz ±5Hz > 0.98 ≤ 7%
≤ 5%
BY PASS Voltage range Frequency range
180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode) Selected frequency ±5 % (user configurable)
BATTERIES Recharge time
4-6h
OUTPUT Rated voltage
220/230/240 Vac selectable
Static variation
1,5 %
Dynamic variation Wave form
≤ 5% in 20ms Sinewave
Voltage distortion with linear load
< 3%
Voltage distortion with non-linear
< 6%
Frequency
50/60 Hz selectable
Crest factor
3:1
OVERLOAD CAPACITY 100% < Load < 110%
1’
100% ≤ Load < 150%
4s
Load > 150%
0.5 s
MODELS
DLD 330
DLD 400
DLD 500
DLD 600
ENVIRONMENTAL Efficiency
92%
Line-interactive/Smart Active Efficiency
98%
Operating temperature
0 ÷ 40 °C
Humidity Protection
< 95% non condensing Overload - short-circuit - overvoltage - undervoltage - temperature - low battery
Compliance
EN 62040-1-1; Directives 73/23/EEC and 93/68/EEC; EN62040-2; Directive 89/336/EEC; 92/31 EEC; 93/68 EEC; EN62040-3
Colour
metallic grey (silver)
Noise Accessories provided